33kV VCB Panel/Switchboard
Our Medium voltage panel or switchboard (MV panel or switchboard) is primarily designed for 33kV applications, ensuring reliable power distribution and protection. The 33kV VCB panel or switchboard integrate Vacuum Circuit Breakers (VCB), Current Transformers (CT), Potential Transformers (PT), Relays, and Meters to safeguard feeders and transformers efficiently. Available in 800A – 20/18.4kA, 1250A – 26.3kA, and ≥1600A – 40kA, this panel or switchboard provides customizable breaker configurations to meet diverse site requirements. While predominantly designed as indoor units, it can be tailored for outdoor installations based on specific environmental needs.
33kV VCB Panel Specifications
Purpose | Feeders of Transformer Switching/Control and Protection |
Voltage | 3.3 to 33kV AC |
STR | As Per Transformer of Client's Requirements |
Current Rating | Up to 3200A |
Breaker Type | Vacuum (draw out or fixed type) |
Reference Standard | IS/IEC 62271 - 200 |
Maximum Transporting Length | 1000mm |
Ingress Protection (IP) | 4X |
Busbar Material | Aluminium or Copper (as Per Client's Requirements) |
Busbar Insulation | Air Insulated |
Cublicle Enclosure Material | CRCA/Aluzinc/GP Sheets |
Sheet Thickness | Main body 2.0 mm and partitions 1.5mm |
Painting | Powder Coating Thickness between 60-80 microns |
Wiring | Copper flexible wires as per rating required with sleeved lugs, number ferules, phase color coding |
Current Transformer | Resin Cast CT with rated primary and secondary as per relays and meters with required VA burden and class of protection and metering |
Potential Transformer | Resin Cast PT with rated primary and secondary as per relays and meters with required VA burden and class of protection and metering |
Protection Relays | As per requirement of the feeder/transformer including auxiliary relays |
Metering | As per requirement of the feeder/transformer like Ampere, Voltage, TVM or equivalent parameters |
Indications/Annunciations | For status of the panel like ON, OFF or TRIP |
Auxiliary Supply | DC 24 to 220V and AC 110V to 415V as per requirement of the customer |
Main Power Connection Terminals | Cable entry from Top or Bottom |